A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
3.27.1 Phase I Emergency Recall Operation After Device Actuation
|
x
|
x
|
2nd and 3rd floor devices not permanently installed (ceilings not installed, devices hanging by their wiring).
|
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
x
|
|
A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Articles or material not necessary for the operation of the elevator shall not be stored in the Elevator Machine Room.
|
7/25/2022
|
A17.1-2016 : Elevators
|
5.12 - Car Buffer
|
3.6.3
|
x
|
|
Buffer spring height does not allow for minimum overtravel of 3.75".
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
2.7.1
|
x
|
|
Fire caulk around conduit penetrations, replace damaged ceiling tiles in machine room.
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
3.1
|
x
|
|
Fire caulk hoistway and pit fire penetrations.
|
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Install outlet/switch covers.
|
|
A17.1-2016 : Elevators
|
5.11 - Plunger and Cylinder
|
3.18.3.3
|
x
|
|
Jack/cylinder does not allow full compression of buffer springs before cylinder bottoms out in jack.
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone does not connect.
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5
|
x
|
|
Pit lighting shall not be less than 10fc.
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.6 Sump Pump Covers
|
x
|
|
Sump cover to be relatively flush with floor.
|
|