A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
MUST MAKE PHONE OPERABLE
|
|
|
A17.1-2016 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
2.4.2
|
x
|
|
ROPES MUST BE SHORTEND CURRENTLY 2 7/8"
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.2-2.27.8
|
x
|
x
|
Phase I will not put elevator on phase I operation--this unit is exempt from smoke detectors due to enviroment
|
8/27/2019
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980)
|
8.6.10.1
|
x
|
x
|
Because of atmospheric conditions smoke are not used however Phase I & II still need to operate as designed, if not corrected withen 30 days the elevator will be RED TAGGED
|
11/3/2020
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
electrical raceway on car top wires grounding needs repaired and raceway resecured
|
9/30/2021
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)6
|
|
|
reopening device is not working
|
9/30/2021
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)7
|
|
|
Door pressure exceeds 30lbs
|
9/30/2021
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
hall door gibs missing on floors 2,3 & 5
|
9/30/2021
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
needs current certificate posted in machine room
|
9/30/2021
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.2 - Car top light and outlet
|
8.11.2.1.3(b)
|
|
|
Inspection station light needs guarded
|
9/30/2021
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980)
|
8.6.10.1
|
x
|
x
|
Ref A17.1- 6.1.2(a)(4) Phase I Recall failed. This Violation was noted on 8/27/19 annual inspection & had not been corrected. Must Re-inspect when Violation is Corrected. Placed a Red Tag and locked out the Equipment.
|
9/30/2021
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
electrical raceway on car top wires grounding needs repaired and raceway resecured
|
12/2/2021
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)6
|
|
|
reopening device is not working
|
12/2/2021
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)7
|
|
|
Door pressure exceeds 30lbs
|
12/2/2021
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
hall door gibs missing on floors 2,3 & 5
|
12/2/2021
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
needs current certificate posted in machine room
|
12/2/2021
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.2 - Car top light and outlet
|
8.11.2.1.3(b)
|
|
|
Inspection station light needs guarded
|
12/2/2021
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
electrical raceway on car top wires grounding needs repaired and raceway resecured
|
3/30/2022
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)6
|
|
|
reopening device is not working
|
3/30/2022
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)7
|
|
|
Door pressure exceeds 30lbs
|
3/30/2022
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
hall door gibs missing on floors 2,3 & 5
|
3/30/2022
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
needs current certificate posted in machine room
|
3/30/2022
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.2 - Car top light and outlet
|
8.11.2.1.3(b)
|
|
|
Inspection station light needs guarded
|
3/30/2022
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
ASME A17.1 Section 2.27.3.2.3 could not be verified due to the Fire Alarm Personnel were not available on the day of the test. Did not Red Tag elevator has not been turned over for service. The reinspection is still in process due to Electronic Drive issues,
|
1/31/2024
|
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
x
|
|
ASME A17.1 Section 2.7.3.4.1(a)(b) Door Closure shall be added and the locking mechanism requires changed.
|
1/31/2024
|