ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.3 - Operating control devices
|
8.11.2.1.1(c)
|
|
|
Remove unused "Access" switch in COP or add outside hoistway switches.
|
12/4/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
2-way communication device shall work and give proper location. Unresponsive with main power off.
|
10/31/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.8 - Door closing force
|
8.11.2.1.1(h)
|
x
|
|
Reduce door pressure to 30# max
|
8/14/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.8 - Door closing force
|
8.11.2.1.1(h)
|
x
|
|
Reduce door pressure to 30# Max (2019 and 2020)
|
1/22/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.8 - Door closing force
|
8.11.2.1.1(h)
|
x
|
|
Reduce door pressure to 30# Max (2019 and 2020)
|
1/22/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
MCP shall be kept in equipment room, including Testing Procedure and Fire service testing log, recorded monthly.
|
12/4/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.13 - Windows, projections, recesses, and setbacks
|
8.11.2.1.3(s)
|
|
|
Secure facia above top floor door
|
12/4/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame.
|
12/4/2020
|