Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Need to pump oil from pit and clean. 3/18/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.30 - Hydraulic Power Unit 8.11.3.1.2(m) No No The main starter relay malfunctioned when performing the annual test. The relay shall be repaired and a reinspection will be required to complete the annual inspection. 3/18/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No The elevator machine room door shall be repaired to be self-closing and self-locking and shall be operable from the interior space without the use of a key. The machine room door shall remained closed and accessible to authorized personnel only. 3/18/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No The ventilation HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. 3/18/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Permanent means of temperature control are inoperable and shall be repaired or replaced. 2/18/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Sight guard on hoistway doors at at the top landing is loose and shall be replaced or repaired. 2/18/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.7 Record of Oil Usage No No Accurate written oil loss / replacement records shall be kept as part of maintenance control program 2/18/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems No No Replace missing hoistway door gib on 2nd floor door 12/12/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A cop of the current state operating certificate needs to be properly displayed in machine room 11/26/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room door is missing keeper in door jamb. 11/26/2023
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No control valve & pump unit leaks excessively causing pans under pump unit to overflow. Remove oil from pans, remove oil soaked pads from machine room, clean floor and repair leaks to prevent this condition. 2/18/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate needs to be properly displayed in machine room. 11/26/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room door is missing keeper in door jamb. Replace same. 11/26/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance No No EXCESSIVE OIL LEAKING FROM CONTROL VALVE 2/18/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No NO MCP IN MACHINE ROOM 12/12/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No The ventilation HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. 2/18/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams No No WIRE RACEWAY COVERS MISSING - EXPOSED WIRNG 12/12/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No PHASE ONE KEY SWITCH BEZEL ILLEGIBLE 12/12/2022
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No PHASE ONE INSTRUCTIONS MISSING 12/12/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No CAR TOP LIGHTING INADEQUATE 12/12/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No MACHINE ROOM DOOR NOT SELF CLOSING / LOCKING 2/18/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in the machine room 12/12/2022
MO Minimum : Elevators (I) - Pits (I)1 No No Remove full 5 gallon oil container from pit, clean pit 12/12/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Cartop need cleaning 12/12/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room door is missing keeper in door jamb, replace same 2/18/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Fire service phase I keyswitch bezel is illegible, needs to be replaced 12/12/2022
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Control valve & pump unit leaks excessively causing pans under pump unit to overflow. Remove oil from pans, remove oil soaked pads from machine room, clean floor and repair leaks to prevent this condition. 2/18/2026
conversion conversion conversion - reinspect Yes No Front door restrictor shall work - re-inspection required 9/6/2018
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes Yes Car does not go into Phase II fire service, Red-tagged, Re-inspection required 3/17/2026
MO Minimum : Elevators (H) - Machine Rooms (H)4 Yes No Control valve and pump unit leaks EXCESSIVELY, causing pans under pump unit to overflow. Remove oil from pans, remove oil soaked pads from machine room floor, clean floor and repair leaks to prevent this condition. Repair and reinspect in 14 days 3/29/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Rear doors ceased operating during testing. Perform fire service tests. Re-inspection required 6/27/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) Yes No EXCESSIVE CLOSING FORCE ON REAR DOORS 12/8/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Yes No MISSING GIBB ON 2ND FLOOR HOISTWAY DOOR 12/8/2022