Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Permanent means of temperature control are inoperable and shall be repaired or replaced.
conversion conversion conversion - reinspect Yes No Fron car door restrictor shall work 9/6/2018
MO Minimum : Elevators (I) - Pits (I)1 No No Pump oil from pit and clean. 3/18/2021
conversion conversion n/a No No Top of car light needs to be protected 3/18/2021
conversion conversion n/a No No Top two floors of duct cover needs to be installed. Top limit tree box needs cover to be installed. 3/18/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No MCP MISSING FORM MACHINE ROOM 12/12/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.5 Code Data Plate No No Code Data Tag missing 12/12/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams No No Missing Wire raceway covers missing - exposed wiring 12/12/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No The ventilation HVAC unit in the machine room is INOP 12/12/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Cartop lighting inadequate 12/12/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in the machine room 12/12/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Cartop needs cleaning 12/12/2022
MO Minimum : Elevators (H) - Machine Rooms (H)8 No No Replace missing wireway cover in machine room over controller 12/12/2022
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Control valve and pump unit leaks oil excessively, causing pans under pump unit to overflow. Remove oil from pans, remove oil soaked pads from machine room floor, clean floor and repair oil leaks to prevent this condition. 3/18/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.7 Record of Oil Usage No No Accurate oil loss / replacement records shall be kept as part of maintenance program for each elevator 3/18/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be properly displayed in the machine room 3/18/2026
MO Minimum : Elevators (H) - Machine Rooms (H)8 No No Replace missing wireway cover in machine room over controller 3/18/2026
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No control valve & pump unit leaks excessively causing pans under pump unit to overflow. Remove oil from pans, remove oil soaked pads from machine room, clean floor and repair leaks to prevent this condition. 3/18/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Repair/ replace inoperative HVAC unit in machine room 3/18/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate needs to be properly displayed in machine room. 3/18/2026
MO Minimum : Elevators (H) - Machine Rooms (H)8 No No Replace missing wireway cover in machine room over controller. 3/18/2026
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Control valve and pump unit leaks oil excessively, causing pans under pump unit to overflow. Remove oil from pans, remove oil soaked pads from machine room floor, clean floor and repair oil leaks to prevent this condition. Failed 15 minute standing test. Repair in 14 days or redtag 3/18/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Repair/replace inoperative HVAC unit in machine room 3/18/2026