Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency light and bell do not operate.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection No No Pit can is overflowing. Pit can shall not be permitted to overflow. 6/15/2020
MO Minimum : Elevators (I) - Pits (I)1 No No Remove hydraulic oil from pit floor. Pit floors shall be kept clean and dry. 6/15/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Provide written documentation inside machine room of quantity of hydraulic fluid added to system and emptied from pit can. 6/15/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Maintenance Control Plan records for the elevator need to be viewable on site. 6/15/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency light and bell do not operate 10/21/2021
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Pit light does not illuminate 10/28/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation No No No maintenance control plan 10/28/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No No maintenance records on site 10/28/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current state operating certificate inside the machine room 10/28/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room access door needs to be self-locking and non-defeatable 10/28/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Provide certified type ABC fire extinguisher inside the machine room 10/28/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance No No Replace plunger seals. Plunger seals leak excessively and pit collection container has overflowed. 10/28/2021