Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars clean up oil on the car top, it is starting to leak into the cab 3/6/2023
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Car Emergency System (Re-Inspection) x emergency light battery is dead, replace battery 5/25/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x the alarm bell did not work on normal power 5/25/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x emergency phone speaker was barely audible, could not hear the operator at all 3/17/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Perform monthly fire service test and post a log in the machine room 3/13/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.5 - Traveling cables 2.8.1 x traveling cable jacket is worn through, bare wires exposed, replace traveling cable 6/20/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing monthly fire service test log in the machine room was last filled out on December 2021, could not find a 2022 or 2023 fire service test log in the machine room 3/6/2023
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation monthly fire service test log has not been filled out since June 2021 5/25/2022