ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Perform monthly fire service test and post a log in the machine room
|
3/13/2020
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters’ Emergency Operation Documentation
|
|
|
monthly fire service test log has not been filled out since June 2021
|
5/25/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
|
|
monthly fire service test log in the machine room was last filled out on December 2021, could not find a 2022 or 2023 fire service test log in the machine room
|
3/6/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
clean up oil on the car top, it is starting to leak into the cab
|
3/6/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.5 - Traveling cables
|
2.8.1
|
x
|
|
traveling cable jacket is worn through, bare wires exposed, replace traveling cable
|
6/20/2024
|
A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Car Emergency System (Re-Inspection)
|
x
|
|
emergency light battery is dead, replace battery
|
5/25/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
emergency phone speaker was barely audible, could not hear the operator at all
|
3/17/2021
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
the alarm bell did not work on normal power
|
5/25/2022
|