Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)12 (Door open zones) No No Door restrictor needs to work. Reinspection required. 1.18 10/14/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Static test failed, oil leaking through valve. 2.42 9/10/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone not working. 1.6 10/14/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)12 (Door open zones) Yes No Car door restrictor does not work. 6/9/2020
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes Fire service Phase I key switch is labeled incorrectly. Repair and reinspect within 30 days. 6/9/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No OSV is not sealed and must have a cat 5 weight test performed within 90 days or less 12/1/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Unit failed 15 minute standing test, suspect leaking back through control valve and machine room shut off. Did not leak down when pit shutoff valve closed 9/21/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Unit failed 15 minute standing test, suspect leak back through control valve and machine room shut off. Did not leak down when pit shut off valve closed 5/19/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems No No Door operator needs repair. 4/10/2025
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal Yes No The hall fire hat jewel must illuminate when on fire service operation.
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational on auxiliary power.
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No The machine room shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No There are two red key-switches marked "stop" in the car operating panel. Only one is operable. The inoperable key-switch shall be replaced or repaired and marked for the function it serves or shall be removed and the hole covered.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes Yes The car leaked excessively during the static test required by A17.1 2016 8.6.5.14.2. It was determined that the oil is leaking back into the tank. Unit RED-TAGGED and not to be returned to service until repaired and tested.