Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)12 (Door open zones) Door restrictor needs to work. Reinspection required. 1.18 10/14/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Static test failed, oil leaking through valve. 2.42 9/10/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV is not sealed and must have a cat 5 weight test performed within 90 days or less 12/1/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Unit failed 15 minute standing test, suspect leaking back through control valve and machine room shut off. Did not leak down when pit shutoff valve closed 9/21/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Unit failed 15 minute standing test, suspect leak back through control valve and machine room shut off. Did not leak down when pit shut off valve closed 5/19/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone not working. 1.6 10/14/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)12 (Door open zones) x Car door restrictor does not work. 6/9/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x x Fire service Phase I key switch is labeled incorrectly. Repair and reinspect within 30 days. 6/9/2020