MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site.
|
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)12 (Door open zones)
|
x
|
|
Car door restrictor does not work.
|
6/9/2020
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
Door operator needs repair.
|
4/10/2025
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)12 (Door open zones)
|
|
|
Door restrictor needs to work. Reinspection required. 1.18
|
10/14/2019
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone not working. 1.6
|
10/14/2019
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Fire service Phase I key switch is labeled incorrectly. Repair and reinspect within 30 days.
|
6/9/2020
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
OSV is not sealed and must have a cat 5 weight test performed within 90 days or less
|
12/1/2021
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Static test failed, oil leaking through valve. 2.42
|
9/10/2020
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
x
|
The car leaked excessively during the static test required by A17.1 2016 8.6.5.14.2. It was determined that the oil is leaking back into the tank. Unit RED-TAGGED and not to be returned to service until repaired and tested.
|
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.3a(8) Visual and audible signal
|
x
|
|
The hall fire hat jewel must illuminate when on fire service operation.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational on auxiliary power.
|
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
The machine room shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
There are two red key-switches marked "stop" in the car operating panel. Only one is operable. The inoperable key-switch shall be replaced or repaired and marked for the function it serves or shall be removed and the hole covered.
|
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Unit failed 15 minute standing test, suspect leak back through control valve and machine room shut off. Did not leak down when pit shut off valve closed
|
5/19/2022
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Unit failed 15 minute standing test, suspect leaking back through control valve and machine room shut off. Did not leak down when pit shutoff valve closed
|
9/21/2021
|