Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Control valve pressure relief setting is not sealed. Perform required testing and seal within 30 days, on or before 9/11/20 5/19/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)12 (Door open zones) Door restrictor needs to work. 1.18 Reinspection Required. 10/14/2019
MO Minimum : Elevators (S) - Fire Service (S)1 x x Fire service Phase I key switch is labeled wrong. Repair and reinspect within 30 days. 6/9/2020
MO Minimum : Elevators (F) - Electrical Switches (F)3 x Need to replace alarm button. 1.3 10/14/2019
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit lighting is not working. 9/26/2025
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal x The hall fire hat jewel must illuminate when on fire service operation.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational on auxiliary power.
MO Minimum : Elevators (H) - Machine Rooms (H)2 The machine room shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The relive valve setting shall be tested. The test is incomplete due to ID 5804 being red-tagged.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts There is a hole in the car operating panel due to a missing key-switch. The key-switch shall be replaced or the hole shall be covered.
MO Minimum : Elevators (I) - Pits (I)1 Water and oil shall not be allowed to accumulate on pit floors. There is oil on the pit floor possibly from a leaky fitting.