MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
cortop work light bulb is missing, install a new bulb
|
1/3/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
|
|
could not find the 110 volt breaker for the elevator cab lights, could not test emergency lights and alarm on battery power
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
machine room fire extinguisher inspection tag is from 2020, have the fire extinguisher inspected and tagged annually
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
maintain dry pit, at the time of the inspection there was standing water in the pit
|
2/11/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
provide key onsite for the fire service keyswitch, could not test fire service
|
3/28/2019
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
repair fire service phase 1 keyswitch, it did not recall the elevator
|
8/6/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Repair the top of car inspection station, it would not run in the down direction
|
2/11/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
replace emergency light battery, it is dead
|
2/11/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
|
|
replace the emergency light battery, it is dead
|
3/28/2019
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
standing water in the pit, maintain a dry pit
|
1/3/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
the location of the 110 volt breaker for the elevator cab lights is not marked down in the machine room, could not find breaker for the lights
|
1/3/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
The Maintenance Control Program (MCP) On-Site documents are not in the machine room.
|
1/3/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
the pit shall be kept dry.
|