Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting either replace the drop ceiling panels or install covers on the light tubes to prevent breakage 5/20/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting instal covers on cab light tubes so they are guarded to prevent breakage 5/20/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Adjust the door restrictor so it works 7/31/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x emergency lights did not come on, alarm bell worked on battery power 7/31/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records does not have Maintenance Control Program (MCP) documents in the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates fire service phase 2 instruction sign can no longer be read, provide fire service phase 2 instruction sign that matches the operation of this elevator (2.27.7.2)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x emergency phone did not work, provide working phone line 7/31/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Adjust door restrictor so it works properly
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements replace missing jamb braille 5/20/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers provide fire extinguisher with updated inspection tag, the one that is in the machine room has an expired inspection tag 5/20/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers provide a ABC fire extinguisher convenient to the access door 12/15/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates replace missing hoistway jamb braille tag at 2nd floor 12/15/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records The Maintenance Control Program (MCP) On-Site documents are not in the machine room. 1/3/2022
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 (Re-Inspection) x settled 2 inches during set test, didn't move with the gate valve close, repair or replace control valve 7/31/2023
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log monthly fire service test log is not being filled out monthly
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log update firefighters'service operation monthly test results 12/15/2020
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log The firefighters service test log is not being filled out monthly. 1/3/2022
MO Minimum : Elevators (S) - Fire Service (S)1 x x the fire service phase 2 operating instructions do not match the operation of the elevator, provide sign with the correct operating instructions 3/12/2020
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Need to perform and post monthly fire service test log in the elevator machine room 5/20/2020