Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.7 Record of Oil Usage No No could not find a oil record log in the machine room 1/3/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No could not find the sign with directions to the location of the elevator light disconnect, could not find breaker for the 110 volt cab lights 1/3/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No Replace burnt out car top light bulb 10/27/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No In car stop switch is broken, repair stop switch on the car operating panel and remove jumper on the controller
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No could not find Maintenance Control Program (MCP) documents in the machine room 10/27/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No The Maintenance Control Program (MCP) On-Site documents are not in the machine room. 1/3/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No car top work light was burnt out, Replace light bulb 1/3/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Only one emergency light bulb worked, replace burnt out emergency light bulb
MO Minimum : Elevators (H) - Machine Rooms (H)8 No No the location of the 110 volt breaker is not written down in the machine room, could not find disconnect, could not test emergency light battery system 10/27/2025
MO Minimum : Elevators (H) - Machine Rooms (H)6 No No label the controller, disconnect, cartop, pit, and car operating panel Elevator #3 1/3/2022
MO Minimum : Elevators (I) - Pits (I)1 No No clean the debris from pit 2/23/2021
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No did not find monthly fire service test log in the machine room 10/27/2025
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No The firefighters service test log is not being filled out monthly. 1/3/2022
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Need to perform and post monthly fire service test log in the elevator machine room 11/25/2019
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No fire service phase 1 did not work at all, turned keyswitch to on position and the elevator remained on normal operation, repair and retest fire service 8/15/2022
MO Minimum : Elevators (S) - Fire Service 211.8 Switch Keys No No Fire service key is not the same as the other two elevators, change the fire service key to the same key used on the other two elevators
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No fire service phase 2 did not work at all, could not close the doors to go to other floors 1/15/2019