Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements car top work light was burnt out, Replace light bulb 1/3/2022
MO Minimum : Elevators (I) - Pits (I)1 clean the debris from pit 2/23/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.7 Record of Oil Usage could not find a oil record log in the machine room 1/3/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records could not find Maintenance Control Program (MCP) documents in the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates could not find the sign with directions to the location of the elevator light disconnect, could not find breaker for the 110 volt cab lights 1/3/2022
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log did not find monthly fire service test log in the machine room
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x fire service phase 1 did not work at all, turned keyswitch to on position and the elevator remained on normal operation, repair and retest fire service 8/15/2022
MO Minimum : Elevators (S) - Fire Service (S)1 x fire service phase 2 did not work at all, could not close the doors to go to other floors 1/15/2019
MO Minimum : Elevators (H) - Machine Rooms (H)6 label the controller, disconnect, cartop, pit, and car operating panel Elevator #3 1/3/2022
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Need to perform and post monthly fire service test log in the elevator machine room 11/25/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Replace burnt out car top light bulb
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log The firefighters service test log is not being filled out monthly. 1/3/2022
MO Minimum : Elevators (H) - Machine Rooms (H)8 the location of the 110 volt breaker is not written down in the machine room, could not find disconnect, could not test emergency light battery system
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records The Maintenance Control Program (MCP) On-Site documents are not in the machine room. 1/3/2022