Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone does not operate 6/29/2022
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits PIT LIGHT NOT WORKING
A17.1-1996 : Elevators 4.5 - Access to Hoistway 111.6 REMOVE BOXES AND MATERIAL FROM IN FRONT OF 1st FLOOR REAR HOISTWAY DOOR
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x EMERGENCY LIGHT DID NOT WORK
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current state operating certificate inside the machine room 4/7/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state operating certificate inside machine room 5/11/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) Wiring diagrams shall be kept on site in the machine room. 4/7/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Post In Case of Fire signage next to corridor call station at each landing 4/7/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.11.1 Firefighters' Emergency Operation & Documentation Test and log firefighter operation monthly 4/7/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance replace plunger seal. 11/24/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Cylinder drain line needs to drain into pit collection container of no more than 5 gallon capacity 5/11/2021