Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation Provide MCP 8/26/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Phase 1 switch broken, replace. Perform testing. Provide testing of phase 1 and 2 operation. Record results in MCP 8/26/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing x Over speed valve not sealed or tagged. Must be cat 5 tested 1/11/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV in pit is not sealed, provide testing per MFG. Leave written procedures on site. Tag and seal upon completion 8/26/2022