MO Minimum : Elevators
|
(A) - Hoistways
|
(A)1
|
|
|
1st floor hoistway bottom door panel bent in, excessive gap between door and sill, straighten or replace door panel
|
10/30/2024
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone was not answered, emergency phone is to be answered 24/7
|
10/2/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
First floor hoistway door Astragal needs to be replace
|
10/30/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Front and rear Car gate astragals need to be replaced
|
10/30/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Front side warning strobe is not working, repair strobe
|
10/30/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
Install lockable pullbox cover over hoistway door unlocking device at landing 10 E
|
7/2/2021
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.10.2.2.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone line monitoring verification does not function.
|
7/2/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Pit light does not illuminate. Repair pit lighting
|
11/19/2018
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(d)
|
x
|
|
Post alteration acceptance metal tag with the applicable code requirements of section 8.10, date of test, name of person performing the test, inspector witnessing test, including inspectors ID number and certifying organization.
|
7/2/2021
|
A17.1-2016 : Elevators
|
2.14 - Code data plate
|
8.7.1.8
|
x
|
|
Post code data plate on controller listing code and edition in effect at time of alteration and requirements in section 8.7 that were applicable to the alteration.
|
7/2/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Post fire service instructions inside and outside the elevator
|
11/9/2018
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.7.2 Periodic Test Record (Test Tags)
|
|
|
Provide and attach annual no load safety test tag.
|
10/23/2023
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.4
|
|
|
Provide clear access to pit access door, walk in pit application.
|
10/23/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.5 Code Data Plate
|
|
|
Provide code data plate reflecting the sections of 8.7 that were modernized or altered.
|
10/23/2023
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)10
|
|
|
Provide lockable access point to access the top of the car from the top landing, pit access ok.
|
10/23/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.7.2 Periodic Test Record (Test Tags)
|
|
|
Provide permanent metal test tag reflecting annual inspections in machine room.
|
10/23/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Rear door reset button on the car operating panel is missing and needs to be replaced
|
10/30/2024
|
A17.1-2016 : Elevators
|
1.3 - Operating control devices
|
2.26.1
|
|
|
Rear door reset button on the car operating panel is missing and needs to be replaced (open hole in the car operating panel)
|
10/23/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Remove standing water on machine room floor. Condensation drain on machine room air conditioner is plugged
|
10/1/2019
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Remove trash, debris, and elevator components from pit.
|
10/23/2023
|
A17.1-2016 : Elevators
|
3.2 - Car top light and outlet
|
2.14.7.1.4
|
|
|
Replace car top light bulb, it did not turn on
|
10/23/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.11 Runby (Re-Inspection)
|
x
|
|
Shorten hoist ropes for proper runby. Runby is less than 6 inches.
|
7/2/2021
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
Shorten main hoisting ropes, only 1" of CW runby in the pit.
|
6/5/2023
|
A17.1-2016 : Elevators
|
3.9 - Floor and emergency identification numbering
|
2.29.2
|
|
|
The only rear opening hoistway door that is labeled on the hoistway side is floor 9, label all hoistway doors on the rear side
|
10/23/2023
|