Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.4 - Normal terminal stopping devices 3.25.1 x The bottom directional limit failed to activate. Upon further investigation it has been determined that the bottom runby for this unit is insufficient to allow the limit to activate properly.
A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 3.4.2 x The bottom runby is insufficient, currently the runby is .5 inches. The minimum required runby is 3 inches. The runby shall be corrected or a variance may be needed.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Remove scavenger pump from pit. Provide code required oil collection means. 11/5/2020