Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Remove scavenger pump from pit. Provide code required oil collection means. 11/5/2020
A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 3.4.2 x The bottom runby is insufficient, currently the runby is .5 inches. The minimum required runby is 3 inches. The runby shall be corrected or a variance may be needed.
A17.1-2016 : Elevators 5.4 - Normal terminal stopping devices 3.25.1 x The bottom directional limit failed to activate. Upon further investigation it has been determined that the bottom runby for this unit is insufficient to allow the limit to activate properly.