Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Post firefighter instructions next to hall fire keyswitch. 7/16/2021
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Test firefighters operation monthly and provide documentation inside machine room. 7/16/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Post emergency evacuation of passengers procedure inside machine room. 7/16/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Gravity flow cylinder drain lines installed in hydraulic tank. Remove drain lines from tank. Each drain line needs its own collection device located in pit, with no more than 5 gallon capacity 7/16/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room access door shall be self-locking 7/16/2021
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light fixture does not illuminate due to previous water damage. 7/16/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state operating certificate inside the machine room 7/16/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No hard copy maintenance records on site 6/7/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room access door shall be self-locking and non-defeatable 11/15/2023
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Replace incorrect firefighter instructions next to hall firefighter keyswitch 11/15/2023
MO Minimum : Elevators (I) - Pits (I)1 Remove standing water in elevator pit 11/15/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 PROVID A SELF LOCKING MACHINE ROOM DOOR 8/12/2024
MO Minimum : Elevators (H) - Machine Rooms (H)4 REMOVE ALL NON-ELEVATOR RELATED ITEMS FROM MACHINE ROOM 8/12/2024
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)2(B) Provide testing of pressure relief valve 7/17/2018
MO Minimum : Elevators (S) - Fire Service (S)1 x Fire service phase 1 operation does not recall elevator. 7/11/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x Emergency phone does not operate. 10/13/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone does not operate. 7/20/2022