Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not operate. 7/20/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No Emergency phone does not operate. 10/13/2020
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room access door shall be self-locking 7/16/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room access door shall be self-locking and non-defeatable 11/15/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No PROVID A SELF LOCKING MACHINE ROOM DOOR 8/12/2024
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No REMOVE ALL NON-ELEVATOR RELATED ITEMS FROM MACHINE ROOM 8/12/2024
MO Minimum : Elevators (I) - Pits (I)1 No No Remove standing water in elevator pit 11/15/2023
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Pit light fixture does not illuminate due to previous water damage. 7/16/2021
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)2(B) No No Provide testing of pressure relief valve 7/17/2018
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No Fire service phase 1 operation does not recall elevator. 7/11/2018
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No Post firefighter instructions next to hall fire keyswitch. 7/16/2021
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No Replace incorrect firefighter instructions next to hall firefighter keyswitch 11/15/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current state operating certificate inside the machine room 7/16/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Post emergency evacuation of passengers procedure inside machine room. 7/16/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No No hard copy maintenance records on site 6/7/2022
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Test firefighters operation monthly and provide documentation inside machine room. 7/16/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection No No Gravity flow cylinder drain lines installed in hydraulic tank. Remove drain lines from tank. Each drain line needs its own collection device located in pit, with no more than 5 gallon capacity 7/16/2021