MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
Emergency phone does not operate.
|
10/13/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not operate.
|
7/20/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Fire service phase 1 operation does not recall elevator.
|
7/11/2018
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Gravity flow cylinder drain lines installed in hydraulic tank. Remove drain lines from tank. Each drain line needs its own collection device located in pit, with no more than 5 gallon capacity
|
7/16/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room access door shall be self-locking
|
7/16/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room access door shall be self-locking and non-defeatable
|
11/15/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
No hard copy maintenance records on site
|
6/7/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Pit light fixture does not illuminate due to previous water damage.
|
7/16/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current state operating certificate inside the machine room
|
7/16/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Post emergency evacuation of passengers procedure inside machine room.
|
7/16/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Post firefighter instructions next to hall fire keyswitch.
|
7/16/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
PROVID A SELF LOCKING MACHINE ROOM DOOR
|
8/12/2024
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)2(B)
|
|
|
Provide testing of pressure relief valve
|
7/17/2018
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
REMOVE ALL NON-ELEVATOR RELATED ITEMS FROM MACHINE ROOM
|
8/12/2024
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Remove standing water in elevator pit
|
11/15/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Replace incorrect firefighter instructions next to hall firefighter keyswitch
|
11/15/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Test firefighters operation monthly and provide documentation inside machine room.
|
7/16/2021
|