Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.1 - Access to machine space 1001.2(b)(1) The machine room door shall be self-locking. 1/29/2020
A17.1-1996 : Elevators 2.14 - Code data plate 1200.6 A code data plate is required. The code data plate shall read: A17.1-1996 1/29/2020
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 10/2/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods 8.6.1.7.5 - Emergency lowering device(ERU) shall be operational. 10/2/2020
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) The machine room fire extinguisher shall have a current test tag. 10/2/2020
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 8/31/2021
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 8/31/2021
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site. Note: The log isn't being filled out monthly. 9/21/2023
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures Firefighters phase one instructions shall be posted near the phase one key-switch in the hallway at the egress floor. 9/21/2023
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)12 x Verify that the heat detector located in the machine room and at the top of the hoistway do not affect the operation of the elevator. 11/27/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Cannot hear the emergency phone operator, fix the volume of the emergency phone so as to hear the operator. 1/27/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Can not hear the emergency phone operator, fix the volume of the emergency phone so as to hear the operator. 11/27/2019