A17.1-1996 : Elevators
|
2.1 - Access to machine space
|
101.3d
|
|
|
Elemonate the dead bolt on the machine room door. Provide a machanical room lock ie. always locked outside never locked inside .
|
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Have your fire extinguisher re-certified it is expired
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Obtain and display a current state operating certificate in the machine room.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Obtain and display a current state operating certificate in the machine room.,
|
4/17/2021
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Provide a working emergency phone. The incoming line is dead, has no dial tone.
|
7/31/2024
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Provide an active phone line
|
10/5/2022
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Repair or replace the emergency phone as it will not dial out.
|
4/16/2021
|
A17.1-1996 : Elevators
|
2.6 - Ventilation
|
101.5b
|
|
|
Repair the HVAC unit in the machine room to provide the minimum ambient temperature satisfactory for the equipment.
|
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7a (3)(a) Standby Illumination in the car. (Re-Inspection)
|
x
|
|
Replace the emergency light battery it won't light the light bulbs.
|
4/16/2021
|