A17.1-2016 : Elevators
|
2.17 - Drive machine brake
|
2.24.8.3
|
x
|
|
2.24.8 - Machine brake holding adjustment shall be properly sealed to prevent unauthorized adjustment.
|
9/15/2023
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
4x4 electrical box in machine room needs to have wiring inside box and cover installed.
|
9/15/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
Adjust upthrust roller bearings for proper clearance to door hanger track. (Multiple floors)
|
9/19/2023
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.4.19.6
|
x
|
|
Building fire alarm initiating devices/panel not currently wired to elevator controller. Must be tested for proper FAID recall operation prior to public use.
|
9/15/2023
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Cartop wireway and 4x4 box covers to be installed.
|
9/19/2023
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Low voltage wiring draped across machine room ceiling. Shall be properly encased and plumbed.
|
9/19/2023
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Low voltage wiring draped across machine room ceiling. Shall be properly encased and plumbed.
|
9/15/2023
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
x
|
|
Machine room shall have GFCI outlet. It is currently a standard outlet.
|
9/15/2023
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
2.7.3.3
|
x
|
|
Machine room upper handrail is loose. Repair or replace.
|
9/15/2023
|
A17.1-2016 : Elevators
|
2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches
|
3.29
|
x
|
|
Machinery, controllers, governors & disconnects shall be numbered conspicuously.
|
9/19/2023
|
A17.1-2016 : Elevators
|
2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches
|
3.29
|
x
|
|
Machinery, controllers, governors & disconnects shall be numbered conspicuously.
|
9/15/2023
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4.1
|
x
|
|
NEC 110.26 - Disconnects do not meet 30" rule i.e. not co-planer.
|
9/15/2023
|
A17.1-2016 : Elevators
|
2.27 - Rope fastenings
|
2.20.9
|
x
|
|
Suspension rope tail ends shall be properly seized/banded.
|
9/19/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Testing is incomplete. Elevator shut down during testing. Category 1 & 5 testing items shall be witnessed.
|
9/15/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.10 Acceptance Inspection and Test
|
x
|
|
Testing is incomplete. Unable to complete tests due to shutdown during test. Items remaining: 125% unintended movement down, 100% safety set, slide, fire service 1 & 2, door force.
|
9/19/2023
|