Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.17 - Drive machine brake 2.24.8.3 x 2.24.8 - Machine brake holding adjustment shall be properly sealed to prevent unauthorized adjustment. 9/15/2023
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x 4x4 electrical box in machine room needs to have wiring inside box and cover installed. 9/15/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Adjust upthrust roller bearings for proper clearance to door hanger track. (Multiple floors) 9/19/2023
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 x Building fire alarm initiating devices/panel not currently wired to elevator controller. Must be tested for proper FAID recall operation prior to public use. 9/15/2023
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Cartop wireway and 4x4 box covers to be installed. 9/19/2023
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x Low voltage wiring draped across machine room ceiling. Shall be properly encased and plumbed. 9/19/2023
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x Low voltage wiring draped across machine room ceiling. Shall be properly encased and plumbed. 9/15/2023
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 x Machine room shall have GFCI outlet. It is currently a standard outlet. 9/15/2023
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.3.3 x Machine room upper handrail is loose. Repair or replace. 9/15/2023
A17.1-2016 : Elevators 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches 3.29 x Machinery, controllers, governors & disconnects shall be numbered conspicuously. 9/19/2023
A17.1-2016 : Elevators 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches 3.29 x Machinery, controllers, governors & disconnects shall be numbered conspicuously. 9/15/2023
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 2.26.4.1 x NEC 110.26 - Disconnects do not meet 30" rule i.e. not co-planer. 9/15/2023
A17.1-2016 : Elevators 2.27 - Rope fastenings 2.20.9 x Suspension rope tail ends shall be properly seized/banded. 9/19/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Testing is incomplete. Elevator shut down during testing. Category 1 & 5 testing items shall be witnessed. 9/15/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x Testing is incomplete. Unable to complete tests due to shutdown during test. Items remaining: 125% unintended movement down, 100% safety set, slide, fire service 1 & 2, door force. 9/19/2023