Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Emergency return unit is inoperable and shall be repaired, or replaced. Reinspection required.
A17.1-1996 : Elevators 2.36 - Hydraulic Cylinders 302.3 1) Where valves and cylinders use packing glands or seals, they shall be examined and maintained to prevent excessive loss of fluid. Packing needs replacing, mechanic had to empty a full 5 gallons of oil from collection bucket. Ref: 1206.5b 4/25/2019
A17.1-1996 : Elevators 5.11 Plunger and Cylinder 1206.5b(4) 1) Where valves and cylinders use packing glands or seals, they shall be examined and maintained to prevent excessive loss of fluid. Packing needs replacing, mechanic had to empty a full 5 gallons of oil from collection bucket. 6/23/2020
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) 1) A record that shall include the maintenance tasks listed with the associated requirements of Section 8.6 identified in the Maintenance Control Program. Ref: 8.6.1.4.1(a)(1) 2/11/2021
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.2 Callbacks (Trouble Calls) Documentation 2) A record of callbacks shall be maintained and shall include the description of reported trouble, dates, time, and corrective action(s) taken that are reported by any means to elevator personnel. Ref: 8.6.1.4.2 2/11/2021
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 3) Overspeed valves, where provided, shall be inspected and tested to verify that they will stop the car, traveling down with rated load. Due for 5-year testing. Ref: 8.6.5.16.5 Note: This Shall Be Done Next Year, during the annual inspection. 2/11/2021
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) x Auxiliary lowering unit inoperable 11/23/2022
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Battery lowering is not working properly. Re-inspection required 12/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods x The battery back-up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors, needs repaired. Re-inspection required 12/10/2024