Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No clean the pit 3/12/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No clean up oil on the car top, it is starting to leak into the cab 3/6/2023
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation No No Monthly fire service test log has not been filled out since June 2021 5/25/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing No No monthly fire service test log in the machine room was last filled out on December 2021, could not find a 2022 or 2023 fire service test log in the machine room 3/6/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 No No New power cable ran through the block wall in the machine room needs to be Fire caulked and flex needs to be secured to the wall. 3/12/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Perform monthly fire service test and post log in the machine room 3/13/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits No No Replace burnt out pit light bulbs 3/12/2026
A17.1-2016 : Elevators 1.12 - Car enclosure 8.11.2.1.1(l) No No replace car riding direction lantern lens that is missing, the hole was covered with duck tape 5/25/2022
A17.1-2016 : Elevators 3.17 - Door and gate equipment 8.11.2.1.3(w) No No replace missing hoistway door pick up roller 5/25/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.11.2.1.5(b) Yes No Shorten ropes, runby is 4”with spring buffers 5/14/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The alarm bell didn’t work on battery power 5/14/2026