Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency Telephone line not active. Must Re-inspect in 14 days. Emergency Alarm bell works.
MO Minimum : Elevators (H) - Machine Rooms (H)2 Elevator Machine room door shall be self closing and self locking Door Closer is missing and locking system is inadequate.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Elevator Corridor call stations shall have signage which reads In Case of Fire Elevators out of Service at each floor.
conversion conversion n/a Governor rope very rudged--replace 7/31/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 2.4.2 x Counterweight runby is less than minimum,Ropes need to be shortened. 12/13/2022