Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Operator could not identify location on phone. 2/14/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Written maintenance control program shall be provided on site. 10/26/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Expired 2/14/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.6.4.13 Door Systems x 1st floor hoist way door missing fire stop. 2/14/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.6 - Governor-rope tension devices 8.11.2.1.5(g) Tail sheave switch is wired into the safety circuit. 7/18/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 x x All key switches shall be operated by one key. 7 days to correct. 10/21/2019