Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(b)(4) No No Post emergency evacuation of passengers form inside control room 2/5/2024
A17.1-2016 : Elevators 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection 8.6.4.20.11 (Re-Inspection) Yes No Need to perform annual test for ascending car and unintended motion 3/25/2022
A17.1-2016 : Elevators 2.13 - Governor, Overspeed Switch, and Seal 8.6.4.20.2 Yes No Test car governor tripping speed and speed at which governor overspeed switch operates 2/5/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No State operating certificate not displayed 2/5/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No phone not dialing out 3/11/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing No No Test and log firefighter operation monthly. 2/5/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current state operating certificate inside the control room. 2/5/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.3.4 No No Machine room access door shall be self-closing 2/5/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Rooms and Machinery Spaces No No Remove non-elevator related material from the control room 2/5/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No State operating certificate not displayed in control room 2/5/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not operate 2/5/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 8.11.2.1.2(a) No No Control room access door needs to be self-closing and self-locking. Need to install door closure and door lock. 2/5/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(g) No No Relocate the mounting of the fire extinguisher in proximity to the control room access door. 2/5/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 8.11.2.1.2(f) No No Control room air conditioner not functioning. Need to provide climate control for the control room. 2/5/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Rooms and Machinery Spaces No No Need to remove non elevator material from machine room. Non elevator material not allowed inside machine room. Material is blocking elevator controller. 2/27/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting Yes No Emergency light does not operate. 1/30/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.26 - Secondary and deflector sheaves 8.6.1.6.2 No No Deflector sheave bearing lacks lubrication and is damaged. Need to replace bearing. 2/27/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) No No FIrefighter cabinet door nees to be labled "FIREFIGHTER OPERATION ". Red lettering minimum of 10 mm tall. 3/25/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing No No Test and log firefighter operation monthly 2/5/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Remove debris from pit. 2/5/2024
conversion conversion n/a No No Provide "Firefighters Operation" sign for firefighter panel on car operating station. Red lettering minimum 10 mm. 1/28/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current operating certificate inside control room . 2/5/2024