ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection)
|
|
|
FIrefighter cabinet door nees to be labled "FIREFIGHTER OPERATION ". Red lettering minimum of 10 mm tall.
|
3/25/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
|
|
Machine room access door shall be self-closing
|
2/5/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current state operating certificate inside the control room.
|
2/5/2024
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current operating certificate inside control room .
|
2/5/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State operating certificate not displayed in control room
|
2/5/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State operating certificate not displayed
|
2/5/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
8.11.2.1.2(a)
|
|
|
Control room access door needs to be self-closing and self-locking. Need to install door closure and door lock.
|
2/5/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.6 - Ventilation
|
8.11.2.1.2(f)
|
|
|
Control room air conditioner not functioning. Need to provide climate control for the control room.
|
2/5/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(g)
|
|
|
Relocate the mounting of the fire extinguisher in proximity to the control room access door.
|
2/5/2024
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2(b)(4)
|
|
|
Post emergency evacuation of passengers form inside control room
|
2/5/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.26 - Secondary and deflector sheaves
|
8.6.1.6.2
|
|
|
Deflector sheave bearing lacks lubrication and is damaged. Need to replace bearing.
|
2/27/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
|
|
Test and log firefighter operation monthly
|
2/5/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
|
|
Test and log firefighter operation monthly.
|
2/5/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Emergency Lighting
|
x
|
|
Emergency light does not operate.
|
1/30/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
phone not dialing out
|
3/11/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not operate
|
2/5/2024
|
A17.1-2016 : Elevators
|
2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection
|
8.6.4.20.11 (Re-Inspection)
|
x
|
|
Need to perform annual test for ascending car and unintended motion
|
3/25/2022
|
A17.1-2016 : Elevators
|
2.13 - Governor, Overspeed Switch, and Seal
|
8.6.4.20.2
|
x
|
|
Test car governor tripping speed and speed at which governor overspeed switch operates
|
2/5/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Remove debris from pit.
|
2/5/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.6.4.8 Machine Rooms and Machinery Spaces
|
|
|
Need to remove non elevator material from machine room. Non elevator material not allowed inside machine room. Material is blocking elevator controller.
|
2/27/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.6.4.8 Machine Rooms and Machinery Spaces
|
|
|
Remove non-elevator related material from the control room
|
2/5/2024
|
conversion
|
conversion
|
n/a
|
|
|
Provide "Firefighters Operation" sign for firefighter panel on car operating station. Red lettering minimum 10 mm.
|
1/28/2019
|