MO Minimum : Elevators
|
(A) - Hoistways
|
(A)1
|
|
|
FLOOR NUMBERS ARE REQUIRED ON HOISTWAY DOORS. NOT LESS THAN 4''
|
9/12/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
No hard copy maintenance records on site
|
7/15/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
Emegency phone does not operate.
|
9/15/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Gravity flow cylinder drain lines installed in hydraulic tank. Need to remove drain lines from tank. Each line needs its own collection device located in pit with a capacity of no more than 5 gallons.
|
10/9/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Post emergency evacuation of passengers procedure inside machine room.
|
10/9/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Replace deteriorated neoprene rollers on limit switches located on top of the elevator. Replacement rollers shall be of equal material, stength, and design.
|
8/12/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room doors shall be self-closing and self-locking.
|
7/15/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Provide hall fire keyswitch identification . Position markings for keyswitch are worn off.
|
10/9/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State operating certificate not displayed
|
7/15/2022
|