Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x Emegency phone does not operate. 9/15/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Gravity flow cylinder drain lines installed in hydraulic tank. Need to remove drain lines from tank. Each line needs its own collection device located in pit with a capacity of no more than 5 gallons. 10/9/2020
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Provide hall fire keyswitch identification . Position markings for keyswitch are worn off. 10/9/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Post emergency evacuation of passengers procedure inside machine room. 10/9/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Replace deteriorated neoprene rollers on limit switches located on top of the elevator. Replacement rollers shall be of equal material, stength, and design. 8/12/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room doors shall be self-closing and self-locking. 7/15/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No hard copy maintenance records on site 7/15/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate not displayed 7/15/2022
MO Minimum : Elevators (A) - Hoistways (A)1 FLOOR NUMBERS ARE REQUIRED ON HOISTWAY DOORS. NOT LESS THAN 4'' 9/12/2024