Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)1 No No FLOOR NUMBERS ARE REQUIRED ON HOISTWAY DOORS. NOT LESS THAN 4'' 9/12/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No the in car emergency phone is not working 3/27/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No Emegency phone does not operate. 9/15/2020
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room doors shall be self-closing and self-locking. 7/15/2022
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No Provide hall fire keyswitch identification . Position markings for keyswitch are worn off. 10/9/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No State operating certificate not displayed 7/15/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Post emergency evacuation of passengers procedure inside machine room. 10/9/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No No hard copy maintenance records on site 7/15/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Replace deteriorated neoprene rollers on limit switches located on top of the elevator. Replacement rollers shall be of equal material, stength, and design. 8/12/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection No No Gravity flow cylinder drain lines installed in hydraulic tank. Need to remove drain lines from tank. Each line needs its own collection device located in pit with a capacity of no more than 5 gallons. 10/9/2020