Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
Missouri Minimum : Platform Lifts (U) - Existing Vertical and Inclined Platform Lifts (U)1 No No The platform lift is striking the hoistway fascia as it travels up and down. Adjust the clearance of the platform from the fascia. 4/13/2020
Missouri Minimum : Platform Lifts (U) - Existing Vertical and Inclined Platform Lifts (U)1 No No The bottom landing self-closing device shall be repaired to operate as designed. 4/13/2020
Missouri Minimum : Platform Lifts (U) - Existing Vertical and Inclined Platform Lifts (U)1 No No Replace broken hoistway panel at top of hoistway to prevent water from getting on lift. 9/15/2021
Missouri Minimum : Platform Lifts (U) - Existing Vertical and Inclined Platform Lifts (U)1 (Re-Inspect) Yes No The platform lift alarm bell is not operating and shall be repaired. 7/21/2022
Missouri Minimum : Platform Lifts (U) - Existing Vertical and Inclined Platform Lifts 10.1.5 Installation Placed Out of Service Yes Yes Platform lift hoistway door would not open at the bottom floor exit. Shut lift down. Re-inspection required 8/6/2024
Missouri Minimum : Platform Lifts (U) - Existing Vertical and Inclined Platform Lifts (U)1 Yes No Emergency alarm shall work, needs repaired. Re-inspection required
Missouri Minimum : Platform Lifts (U) - Existing Vertical and Inclined Platform Lifts (U)1 No No Need to replace missing glass panel at top of enclosure
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Unit not running at time of inspection. Repair and perform all required testing to complete inspection