Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Alarm bell failed to operate during audit. 5/15/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11.1.4(b)(2) Hydraulic elevators Placed out of Service Yes Yes Could not perform pressure test and other required tests 2/5/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11.3.2.2 Cylinders Test shall be performed Yes No Elevator Red Tagged Could not perform pressure tests due to numerous problems with elevator. 2/5/2021
A17.1-2016 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5 Gland Packing and Seals Yes No Must replace Jack Packing Gland to limit oil loss. 8.6.5.5.