Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 7/23/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 7/23/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods 8.6.5.8 - Need to determine if this unit is a single bottom jack. If unit is a single bottom type, corrective action shall be taken. If it is determined this unit is not a single bottom type, documentation shall be kept on-site for elevator personnel to confirm. 7/23/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements During 15 minute standing test the elevator was dropping. The mechanic shut the valve and the car quit dropping likely indicating the oil is leaking back through the valve. The valve needs rebuilt or replaced.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Emergency power operation of the elevator shall be tested to determine conformance with the applicable requirements. 7/9/2021
conversion conversion n/a Back wall needs to be refastened to cab floor. 8/21/2018
conversion conversion n/a Top car inspection station shall work. 8/21/2018