Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 103.2 x Counter weight guards shall extend from a point not more than twelve inches (12") above the pit floor to a point not less than seven feet (7') above the pit floor. 4/14/2023
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 Clean the pit of dirt and debris. 3/30/2023
A17.1-1996 : Elevators 2.27 - Rope fastenings 212 Wedge Rope Socket is anchored incorrectly. When the steel wire rope has been seated in the wedge socket by the load on the rope, the wedge shall be visible, and at least two wire-rope retaining clips shall be provided to attach the termination side to the load-carrying side of the rope. The first clip shall be placed a maximum of 4 times the rope diameter above the socket, and the second clip shall be located within 8 times the rope diameter above the first clip. 3/30/2023
A17.1-1996 : Elevators 2.14 - Code data plate 215 Install a code data plate. It shall read A17.1 - 1996/A17.3 - 1996. 3/30/2023
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 3/30/2023
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 3/30/2023
conversion conversion conversion - reinspect x In car emergency phone does not work. 8/14/2018
conversion conversion n/a Car top hoistway and pit needs housekeeping 12/13/2018