MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 1/20/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 1/20/2023
MO Minimum : Elevators (I) - Pits (I)1 Clean the pit of dirt and debris. 1/20/2023
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)11 Wedge Rope Socket is anchored incorrectly. When the steel wire rope has been seated in the wedge socket by the load on the rope, the wedge shall be visible, and at least two wire-rope retaining clips shall be provided to attach the termination side to the load-carrying side of the rope. The first clip shall be placed a maximum of 4 times the rope diameter above the socket, and the second clip shall be located within 8 times the rope diameter above the first clip. 1/20/2023
conversion conversion n/a suspension ropes excess wear, replace 12/13/2018
conversion conversion n/a car top needs to be cleaned 12/13/2018
conversion conversion n/a hoistway need cleaning 12/13/2018