Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 4.1 - Car platform guard 2.15.9 x Obstruction in pit will not accommodate a 48" platform guard. Customer will need to request a variance. 5/31/2023
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.1 Phase I Emergency Recall Operation x x Test fire service switch at lobby hall station after new one is installed. 5/31/2023
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.3.4 x Provide a self-closing and self-locking machine room door. 5/31/2023
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.3.1 x Provide a permanent step at the machine room entrance. 5/31/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Test standby power when installation is complete. 5/31/2023
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Install hoistway duct covers. 5/31/2023
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Remove temporary wiring from hoistway. 5/31/2023
A17.1-2016 : Elevators 4.2 - Hoistway doors 2.11 x Cover old escutcheon holes in hoistway doors. 5/31/2023
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x Install machine room duct covers. 5/31/2023
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x Remove all temporary wiring from the machine room. 5/31/2023
A17.1-2016 : Elevators 2.14 - Code data plate 8.9 x 8.10.1.1.4 - Provide acceptance test tag permanently attached to controller. 5/31/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements 1.6 - The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. 5/20/2019