MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
1.6 - The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety.
|
5/20/2019
|
A17.1-2016 : Elevators
|
4.1 - Car platform guard
|
2.15.9
|
x
|
|
Obstruction in pit will not accommodate a 48" platform guard. Customer will need to request a variance.
|
5/31/2023
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.1.1 Phase I Emergency Recall Operation
|
x
|
x
|
Test fire service switch at lobby hall station after new one is installed.
|
5/31/2023
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
x
|
|
Provide a self-closing and self-locking machine room door.
|
5/31/2023
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
2.7.3.1
|
x
|
|
Provide a permanent step at the machine room entrance.
|
5/31/2023
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Test standby power when installation is complete.
|
5/31/2023
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Install hoistway duct covers.
|
5/31/2023
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Remove temporary wiring from hoistway.
|
5/31/2023
|
A17.1-2016 : Elevators
|
4.2 - Hoistway doors
|
2.11
|
x
|
|
Cover old escutcheon holes in hoistway doors.
|
5/31/2023
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Install machine room duct covers.
|
5/31/2023
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Remove all temporary wiring from the machine room.
|
5/31/2023
|
A17.1-2016 : Elevators
|
2.14 - Code data plate
|
8.9
|
x
|
|
8.10.1.1.4 - Provide acceptance test tag permanently attached to controller.
|
5/31/2023
|