Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency alarm does not work on normal or battery power. 2/7/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher in machine room is expired. replace or have serviced
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Maintenance control program needs to be updated
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Kellem grip on front car gate reversing edge cable is broken. Replace same
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency alarm does not work on normal or battery power. Re-inspection required 2/7/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher in machine room is expired, replace or have serviced
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Kellum grip on front car gate reversing edge cable is broken, needs to be replaced
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency alarm does not work on normal or battery power. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Kellum grip on front car gate reversing edge cable is broken, replace same
MO Minimum : Elevators (I) - Pits (I)1 Pit needs to be cleaned
MO Minimum : Elevators (I) - Pits (I)1 Pit needs to be cleaned
MO Minimum : Elevators (I) - Pits (I)1 pit needs to be cleaned
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV not sealed. Perform test on valve on or before next annual inspection. 12/19/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.30 - Hydraulic Power Unit 8.11.3.1.2(m) Hydraulic tank is leaking fluid. 2/3/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Written maintenance control program shall be provided on-site for each elevator. 12/19/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Rooms and Machinery Spaces Clean oil from elevator machine room. 2/3/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.14 - Hoistway clearances 8.11.2.1.3(t) Rear hoistway facia is rubbing car gate and cab while car is in flight. Repair facia. 2/3/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 2.12 Hoistway doors have excessive gap when closed (no more than 3/4") at all floors, especially @ 2. Adjust same.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.2 - Car top light and outlet 2.14.7 Cartop light bulb on rear needs replacing
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.2 - Car top light and outlet 2.14.7 Cartop light bulb on rear needs replacing.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.2 - Car top light and outlet 2.14.7 Cartop light bulb on rear needs replacing
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 8.11.2.1.4(e) Repair hoistway access pull box on main landing - it will not lock. 2/3/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 x x Hold position on Phase 2 fire service does not work properly. Thirty (30) days to repair and reinspect. Did not red tag. 2/11/2021
conversion conversion n/a Repair gate reopening devices and light rays on front and rear freight doors 5/1/2019