MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency alarm does not work on normal or battery power. Re-inspection required
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit needs to be cleaned
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
pit needs to be cleaned
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit needs to be cleaned
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.17 - Door and gate equipment
|
2.12
|
|
|
Hoistway doors have excessive gap when closed (no more than 3/4") at all floors, especially @ 2. Adjust same.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.2 - Car top light and outlet
|
2.14.7
|
|
|
Cartop light bulb on rear needs replacing.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.2 - Car top light and outlet
|
2.14.7
|
|
|
Cartop light bulb on rear needs replacing
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.2 - Car top light and outlet
|
2.14.7
|
|
|
Cartop light bulb on rear needs replacing
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Maintenance control program needs to be updated
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Fire extinguisher in machine room is expired, replace or have serviced
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Fire extinguisher in machine room is expired. replace or have serviced
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Kellum grip on front car gate reversing edge cable is broken, needs to be replaced
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Kellem grip on front car gate reversing edge cable is broken. Replace same
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Kellum grip on front car gate reversing edge cable is broken, replace same
|
|
conversion
|
conversion
|
n/a
|
|
|
Repair gate reopening devices and light rays on front and rear freight doors
|
5/1/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.14 - Hoistway clearances
|
8.11.2.1.3(t)
|
|
|
Rear hoistway facia is rubbing car gate and cab while car is in flight. Repair facia.
|
2/3/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.5 - Access to Hoistway
|
8.11.2.1.4(e)
|
|
|
Repair hoistway access pull box on main landing - it will not lock.
|
2/3/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.30 - Hydraulic Power Unit
|
8.11.3.1.2(m)
|
|
|
Hydraulic tank is leaking fluid.
|
2/3/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.6.4.8 Machine Rooms and Machinery Spaces
|
|
|
Clean oil from elevator machine room.
|
2/3/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.2-2.27.8
|
x
|
x
|
Hold position on Phase 2 fire service does not work properly. Thirty (30) days to repair and reinspect. Did not red tag.
|
2/11/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Written maintenance control program shall be provided on-site for each elevator.
|
12/19/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
OSV not sealed. Perform test on valve on or before next annual inspection.
|
12/19/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency alarm does not work on normal or battery power.
|
2/7/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency alarm does not work on normal or battery power. Re-inspection required
|
2/7/2024
|