Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.2 - Car top light and outlet 2.14.7 No No Cartop light bulb on rear needs replacing 2/19/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.2 - Car top light and outlet 2.14.7 No No Cartop light bulb on rear needs replacing
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.2 - Car top light and outlet 2.14.7 No No Cartop light bulb on rear needs replacing. 2/19/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Rooms and Machinery Spaces No No Clean oil from elevator machine room. 2/3/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency alarm does not work on normal or battery power. 2/7/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency alarm does not work on normal or battery power. Re-inspection required 2/7/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency alarm does not work on normal or battery power. Re-inspection required 5/13/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency bell shall be operational. 2/16/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting Yes No Emergency light shall be operational. 2/16/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Fire extinguisher in machine room is expired, replace or have serviced 2/19/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Fire extinguisher in machine room is expired. replace or have serviced 2/19/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 2.12 No No Hoistway doors have excessive gap when closed (no more than 3/4") at all floors, especially @ 2. Adjust same. 2/19/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 Yes Yes Hold position on Phase 2 fire service does not work properly. Thirty (30) days to repair and reinspect. Did not red tag. 2/11/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.30 - Hydraulic Power Unit 8.11.3.1.2(m) No No Hydraulic tank is leaking fluid. 2/3/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Kellem grip on front car gate reversing edge cable is broken. Replace same 2/19/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Kellum grip on front car gate reversing edge cable is broken, needs to be replaced 2/19/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Kellum grip on front car gate reversing edge cable is broken, replace same
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Maintenance control program needs to be updated 2/19/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No OSV not sealed. Perform test on valve on or before next annual inspection. 12/19/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Pit needs cleaned
MO Minimum : Elevators (I) - Pits (I)1 No No Pit needs to be cleaned
MO Minimum : Elevators (I) - Pits (I)1 No No pit needs to be cleaned 2/19/2026
MO Minimum : Elevators (I) - Pits (I)1 No No Pit needs to be cleaned 2/19/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Pit shall be kept clean.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.14 - Hoistway clearances 8.11.2.1.3(t) No No Rear hoistway facia is rubbing car gate and cab while car is in flight. Repair facia. 2/3/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance No No Repair gate clearance on rear. Scraping at 1R and fascia at 3rd-4th floor.
conversion conversion n/a No No Repair gate reopening devices and light rays on front and rear freight doors 5/1/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 8.11.2.1.4(e) No No Repair hoistway access pull box on main landing - it will not lock. 2/3/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Written maintenance control program shall be provided on-site for each elevator. 12/19/2022