Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No 2 top counterweight guide rollers are deteriorated. Replace same 6/4/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 6/4/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Clean cartop 6/4/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Clean elevator car top 6/4/2026
conversion conversion n/a No No Install missing duct covers in hoistway 5/1/2019
MO Minimum : Elevators (I) - Pits (I)1 No No Pit needs to be cleaned 6/4/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Replace damaged counterweight rollers 6/4/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Replace damaged counterweight rollers. top 6/4/2026
MO Minimum : Elevators (A) - Hoistways (A)16 No No Replace missing duct cover in hoistway at first floor 6/4/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Replace missing hoistway door gibbs at 1st & 4th floors 6/4/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Replace missing hoistway door gibbs, 1st and 4th floors 6/4/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Replace missing hoistway door gibs at 4th and 1st floor 6/4/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 2.11 No No Replace missing hoistway door safety retainers at 1st floor 6/4/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Replace missing hoistway door safety retainers at 1st floor 6/4/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Replace missing hoistway door safety retainers, 1st floor 6/4/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.6.3.3.3 Runby & Clearances After Reroping or shortening Yes No Counterweight runby is 0". Shorten hoisting cables to maintain 6" runby. 5/27/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Elevator cab emergency light does not work 3/29/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Elevator cab emergency lights do not work. Re-inspection required 5/13/2025
A17.1-2016 : Elevators 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection 2.19.2 Yes Yes Emergency brake failed unintended movement testing. RED TAGGED. Repair and reinspect 4/26/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Emergency light and alarm does not work on emergency power. 4/26/2023
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device Yes Yes Heat in top of hoistway shall shunt elevator
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes No Hoist ropes are undersized and showing rouge. Replace ropes within 60 days. 4/26/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Perform fire service testing to complete inspection 4/26/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Phone in elevator cab is not working. Re-inspection required 11/3/2022
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device Yes Yes Smoke on 3rd floor shall recall elevator to main fire floor
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes No Suspension ropes are undersized and showing rouge. Replace by 6/4/23 3/29/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No This elevator is due for category 5 testing in 2025. Testing was scheduled for this date but hotel management asked that it be delayed. 6/4/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Unit has emergency generator backup power, which needs to be scheduled and tested to complete inspection. Re-inspection required 5/13/2025