Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.18 - Traction drive machines 8.11.2.1.2(p) x Traction machine leaking oil onto outboard side of drive sheave. Repair leaking sheave. 2/22/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Items still to be tested: finish Cat 5, slide test, pull-out/pull thru, electrical trip speed, mechanical trip speed, brake test, and crush car buffer with full load shall be completed.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency bell shall be operational.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting x Emergency light shall be operational.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Emergency power operation shall be tested.