ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.18 - Traction drive machines
|
8.11.2.1.2(p)
|
x
|
|
Traction machine leaking oil onto outboard side of drive sheave. Repair leaking sheave.
|
2/22/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Emergency Lighting
|
x
|
|
Emergency light shall be operational.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency bell shall be operational.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Emergency power operation shall be tested.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Items still to be tested: finish Cat 5, slide test, pull-out/pull thru, electrical trip speed, mechanical trip speed, brake test, and crush car buffer with full load shall be completed.
|
|