Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Car top needs to be cleaned
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Cartop needs to be cleaned
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Cartop needs to be cleaned
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Emergency generators shall be tested. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x emergency light and alarm in car do not work on back up power. Repair same. Reinspection required within 30 days 2/6/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.6.4.13 Door Systems x Hoistway door at 4th floor appears to have been replaced. Adjust door height so gibbs and safety retainer properly engages sill. Re-inspection required 2/6/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.6.4.13 Door Systems x Hoistway door at 4th floor appears to have been replaced. Inside of door needs to be identified with proper numbering. Re-inspection required 2/6/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.6.4.13 Door Systems x Hoistway door at 4th floor appears to have been replaced. Re-install door restrictors as needed. Re-inspection required 2/6/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.9 - Floor and emergency identification numbering 2.29.2 Hoistway doors on 4th floor appear to have been replaced. Inside of door needs to be identified with proper numbering
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.6.4.13 Door Systems x Hoistway doors on 4th floor appear to have been replaced. Reinstall door restrictors as needed 2/6/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.6.4.13 Door Systems x hoistway doors on 4th floor appears to have been replaced. Adjust door height so gibs and safety retainer properly engages sill 2/6/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.6.4.13 Door Systems x Hostway doors 4th floor appears to have been replaced. Adjust door height so gibbs and safety retainer properly engages sill. Re-inspection required
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.6.4.13 Door Systems x Hostway doors 4th floor appears to have been replaced. Inside of door needs to be identified with proper numbering. Re-inspection required
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.6.4.13 Door Systems x Hostway doors 4th floor appears to have been replaced. Re-install door restrictors as needed. Re-inspection required
MO Minimum : Elevators (I) - Pits (I)1 Pit needs to be cleaned
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Written maintenance control program shall be provided on-site for each elevator. 12/19/2022