Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 2.14.7 x 110 disconnect shall be moved to an accessible location in the Machine Room
A17.1-2016 : Elevators 6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators 2.27.1 x FEO Phase I and II need to be tested when hall risers are installed.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.11.2.1.5(b) x Counterweight buffer is being compressed 2" when car is at a top landing. Shorten suspension ropes to maintain proper counterweight runby. 2/18/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Written maintenance control program shall be provided on-site for each elevator. 12/19/2022